The Tyco 801PHEx 516.800.530 is an intrinsically safe, optical smoke & heat detector. The detector is part of the Tyco 800Ex Intrinsically Safe Series, and is plugged into a Tyco 5BEX Base.
The Tyco 801PHEx is designed to transmit digital signals which represent the status of the optical smoke and heat elements of the detector to a remote MINERVA T2000 Fire Controller. Software within the controller is used to interpret the returned optical and heat values to raise an alarm or other appropriate responses according to the type of detector configured in ‘MX CONSYS’.
The mode of detector may be:
Optical smoke only detector (sensitivity High, Normal or Low)
HPO smoke detector (sensitivity High, Normal or Low)
Heat only rate-of-rise (A1R) detector (no sensitivity selection)
Heat only fixed temperature 60°C (A2S) (no sensitivity selection)
Optical (sensitivity High, Normal or Low) combined with heat fixed temperature 60°C (A2S)
HPO (sensitivity High, Normal or Low) combined with heat fixed temperature 60°C (A2S)