BExCP3A-PB-BExCP3B-PB

E2S BExCP3A-PB/BExCP3B-PB Push Button Manual Call Point


The E2S BExCP3A-PB and E2S BExCP3B-PB Push Button Manual Call Points are approved for Zone 1, 2, 21 and 22 hazardous areas for the control of fire and gas alarm systems. These Manual Call Points with and without monitoring resistors all versions are certified to ATEX and IECEx standards.

The Push Button mechanism is protected by a spring loaded cover therefore the switch requires a 2-action activation. The product is user resettable by rotating the Push Button.

The E2S BEx range features enclosures manufactured from corrosion proof, marine grade, copper free LM6 (A413) aluminium which is phosphated and powder coated.

E2S BExCP3A-PB/BExCP3B-PB Push Button Manual Call Point

Please contact us for more information.
Alternative housing colors are available to meet specific requirements
DIN rail mounted terminal blocks: 8 x 2.5mm²
Metalized polyester “Duty” label
Series and/or end of line resistors.
Classifications: BExCP3A-PB:
II 2G Ex e d IIC T6 Gb
II 2D Ex t IIIC T60°C Db
IP66

BExCP3B-PB:
II 2G Ex e d mb IIC T4 Gb
II 2D Ex t IIIC T70°C Db
IP66
Ambient: Ta = -40°C to +55°C, -40° to +131°F
(+50°C for BExCP3B)
Ingress Protection: IP66
Housing material: Marine grade copper free LM6 Aluminium
Housing finish: Phosphated & powder coated finish: anti-corrosion
Color: RAL3000 RZVed (others available on request)
Cable entries: 2 x M20 clearance top and
1 x M20 clearance side
Back box can be rotated to give
2 x bottom and 1 x side entries
Stopping plugs: 2 x Ex e nylon plugs as standard
Brass and stainless steel plugs optional
Terminals: 6 x 4.0mm² cables