Field of view: |
FS24X-9: 90° cone of vision, ± 45° from on axis
FS24X-2: 110° cone of vision, ± 55° from on axis |
Sensitivity: |
Very high (200 ft.), high (150 ft.), medium (100 ft.)
and low (50 ft.) - switch selectable |
Response time: |
3-5 seconds to 1 sq. ft. n-Heptane fire at 30 m (100 ft.)
3-10 seconds to 1 sq. ft. n-Heptane fire at 60 m (200 ft.) |
Operating voltage: |
24 Vdc nominal (18-32 Vdc) - regulated |
Power consumption: |
Operating: 56 mA @ 24 Vdc nominal
Alarm: 106 mA @ 24 Vdc nominal
Heater: 155 mA – additional
Note: Heater will turn on at 0°F (-17°C) |
Analog output: |
0 - 20 mA stepped - source or sink user selectable |
Visual indications: |
Green LED: Power
Red LED: Alarm
Yellow LED: Fault |
Operating temperature: |
110° Field of view FS24X: -40°C to +85°C, -40°F to +185°F
90° Field of view FS24X: -60°C to +85°C, -76°F to +185°F |
Storage temperature: |
-55°C to +110°C, -67°F to +230°F |
Humidity: |
5 to 98% RH, non-condensing |
Enclosure materials: |
Copper-free powder coated aluminum
or 316 stainless steel |
Enclosure type: |
IP66 and NEMA 4 & 4X |
Shipping weight: |
Aluminum: 1.6 kg (3.6 lbs)
Stainless steel: 3.2 kg (7 lbs) |
Certifications: |
FM:
Class I, Div. 1 & 2, Groups B, C, & D;
Class II, Div. 1 & 2, Groups E, F, & G; Class III
ATEX/IECEx:
II 2 G Ex db IIC T4 (Ta: -60 to +110°C),
T5 (Ta: -60 to +75°C), T6 (Ta: -60 to +60°C),
II 2 D Ex tb IIIC T135°C (FS24X-9, 90° Field of View)
II 2 G Ex db IIC T4 (Ta: -40 to +110°C),
T5 (Ta: -40 to +75°C), T6 (Ta: -40 to +60°C),
II 2 D Ex tb IIIC T135°C (FS24X-2, 110° Field of View)
CE:
Complies with EN6100-6-4 & EN50130-4
INMETRO
CU-TR
SIL Rating:
FMEDA available on request
EN54-10:
FS24X-9 certified 1175a/02 (LPCB);
CPR 0832-CPR-F0516 |