Consilium Salwico NS-AIN1 IP55 Address Unit N11893
The Salwico Consilium NS-AIN1 is an addressable interface loop unit for connection both IS and conventional units, such as smoke, heat or flame detectors, to the analogue fire alarm systems CS3000, CS4000 and NSAC-1.
The Salwico Consilium NS-AIN1 is an addressable interface loop unit for connection both IS and conventional units, such as smoke, heat or flame detectors, to the analogue fire alarm systems CS3000, CS4000 and NSAC-1. Both the address numbers and type of connected detector are set by DIP-switches.
When the units that are connected to the NS-AIN1 are in an alarm condition, a red LED on the PCB will be lit. This will remain lit until the alarm has been reset at the control panel.
The included end of line resistor (ELR-33) has to be connected after the last unit for cable break supervision.
Weight | 1 kg |
---|---|
Inputs |
One for conventional detectors |
Nominal voltage |
24VDC |
Working voltage |
15-35 VDC |
Operating current - supervising |
ID2 15 mA ,ID3 1.5 mA |
Alarm Current |
ID2 15 mA ,ID3 11.5 mA |
Cable Dimension |
8 – 14 mm |
Cable Terminals |
2.5mm2 |
Temperature range |
-25°C to +70°C |
Relative Humidity |
0 to 95% RH |
IP Rating |
IP55 |
Material |
PC/ABS |
Color |
Grey |
Weight |
~300 g |
System/Series |
CS3000 ,CS4000 ,NSAC-1 ,Salwico Cargo ,Salwico Cruise ,Salwico Ro/Pax ,Salwico Workboat ,Salwico Yacht |
Need some help with your project?