Consilium Salwico MCP-A WP SCI IP67 Manual Call Point 5200031-02B

The Salwico MCP-A WP SCI IP67 is an addressable manual call point, designed for use in the Salwico Fire Alarm Systems.

41 in stock (can be backordered)

The Salwico MCP-A WP SCI IP67 is an addressable manual call point, designed for use in the Salwico Fire Alarm Systems. The Salwico MCP-A WP SCI IP67 Manual Call Point 5200031-02B is made out of PC/ABS and the encapsulation, rated IP67, makes it suitable for use in harsh environments. Pressing the glass causes it to crack and activate the fire alarm. A protective plastic coating on the break glass prevents the operator from injury.

An LED on the front of the MCP-A WP SCI IP67 indicates the fire alarm. This LED remains lit until the fire alarm has been reset on the fire alarm panel.

The call point can be tested with a special key, which is included in the delivery.
The address of the Salwico MCP-A WP SCI IP67 Manual Call Point 5200031-02B is set with a DIPswitch

The MCP-A WP SCI also provides short-circuit protection via connections 1-4.

Weight 0.2 kg
Addressable/Conventional Addressable
Nominal voltage 34VDC
Working voltage 20-38 VDC
Operating current - supervising 0.25 mA
Alarm Current 2.5 mA
IP Rating IP67
Temperature range -25°C to +70°C
Relative Humidity 0 to 95% RH
Material PC/ABS
Color Red
Weight ~250 g
Cable Dimension 6 – 12 mm
Certified according to 470
System/Series OEM Extinguish , Salwico Cargo , Salwico Cruise , Salwico LNG , Salwico Navy , Salwico Offshore , Salwico Ro/Pax , Salwico Workboat , Salwico Yacht
SKU: 5200031-02B Categories: , , Tags: ,