STExC1X05R Alarm Horn & Xenon Strobe Beacon
| Maximum output | 113dB(A) @ 1 m +/- 3dB [107dB(A) @ 10ft/3m +/- 3dB] |
|---|---|
| Nominal output | 108dB(A) @ 1m +/- 3dB [104dB(A) @ 10ft/3m] +/- 3dB |
| No. of tones | 64 (UKOOA / PFEER compliant) |
| No. of stages | 4 |
| Volume control | Full range |
| Effective range | 125m/410ft @ 1KHz |
| Voltage DC | 12Vdc (11.5-14Vdc), 24Vdc (20-28Vdc), 48Vdc (42-54Vdc) |
| Voltage AC | 230vac (220-240vac) |
| Stage switching | AC units: common supply line, DC units: negative or positive |
| Energy | 5 Joules (5Ws) |
| Flash rates | 1.5Hz flash (90 fpm), 1Hz flash (60 fpm), Double flash (120 fpm) |
| Eff. Intensity cd | 143 cd* – measured ref. to I.E.S., 250 cd – calculated from energy (J) |
| Peak Candela | 46,976 cd* – measured ref. to I.E.S., 500,000 cd – calculated from energy (J) |
| Lens colours | Amber, Blue, Clear, Green, Magenta, Red & Yellow |
| Tube life | Emissions are reduced to 70% after 5 million flashes |
| Safety Integrity Level | SIL1 and SIL2 Route 2H IEC61508 (2010) |
| Ingress protection | EN60529: IP66 |
| Enclosure material | 316L Stainless Steel |
| Enclosure colour | Red |
| Enclosure finish | Chromate & powder coated finish |
| Cable entries | 3 x M20x1.5mm, Stopping plugs included |
| Measurable gases | Stainless Steel |
| Terminals | 0.5 – 2.5mm2 (20-14 AWG), Pluggable & duplicated terminals |
| Line monitoring | Blocking diode included, EOL Min. 500 Ohm 2w, or 3k3 Ohm 0.5w resistor, or diode (DC versions) can be fitted |
| Ground/Earth stud | M5 |
| Installation temp | -50° to +70°C (-58°F to +158°F) |
| Storage temperature | -50° to +70°C (-58°F to +158°F) |
| Relative Humidity | 95% – Additional tropicalisation is recommended for applications where both high relative humidity and high ambient temperatures exist |
| Weight | 7.2kg/15.87lbs |
Related products