GNExS2H Alarm Horn Sounder

Maximum outputHigh power level: 127dB(A) @ 1 m +/- 3dB [118dB(A) @ 10ft/3m +/- 3dB], Medium power level:119dB(A) @ 1m +/- 3dB [110dB(A) @ 10ft/3m] +/- 3dB
Nominal outputHigh power level: 124dB(A) @ 1m +/- 3dB [115dB(A) @ 10ft/3m] +/- 3dB, Medium power level: 119dB(A) @ 1m +/- 3dB [110dB(A) @ 10ft/3m] +/- 3dB
No. of tones64 (UKOOA / PFEER compliant)
No. of stages4
Volume controlFull range
Effective range>350m/1148ft @ 1KHz
Voltage DC24Vdc (10-30Vdc), 48vdc (38-60Vdc)
Voltage AC230Vac (100-260Vac)
In rush815mA within 4ms @ 24Vdc
Stage switchingAC units:common supply line, DC units: positive or negative
Safety Integrity LevelSIL1 and SIL2 Route 2H IEC61508 (2010)
Ingress protectionEN60529: IP66
Enclosure materialUV stable GRP (glass reinforced polyester)
Enclosure colourNatural Red
Enclosure finishNatural – can be painted in alternative colours
Cable entries2 x M20x1.5mm, Stopping plug included
Measurable gasesBrass, Nickel Plated or Stainless Steel
Terminals0.5 – 2.5mm2 (20-14 AWG), Pluggable & duplicated terminals
Line monitoringBlocking diode included, Diode polarized for use in supervised circuits Blocking diode for reverse polarity monitoring, EOL Min. 500 Ohm 2w, or 3k3 Ohm 0.5w resistor, or diode (DC versions) can be fitted
Ground/Earth studM4
Installation temp-50° to +70°C (-58°F to +158°F)
Storage temperature-50° to +70°C (-58°F to +158°F)
Relative Humidity00%, 99
MTBF DC93.92 years / 822,706 hours – MIL 217
MTBF AC46.66 years / 408,508 hours – MIL 217
WeightDC: 3.00kg/6.6Ibs AC: 3.20kg/7.04Ibs
SKU: E2S-GNExS2H Categories: , , Tag:

Related products

Need some help with your project?