D2xC4 Haz Loc LED/Xenon & Horn Alarm Bar

SourceArray of 4 x High Power Cree LEDs
Eff. Intensity cd180 cd UL1638 General signaling (D2xB1LD2 LED Beacon), 250 cd – calculated from energy (J) (D2xB1X05 5J Xenon Strobe Beacon), 288.8 cd* – measured ref. to I.E.S. (D2xB1X10 10J Xenon Strobe Beacon), 500 cd – calculated from energy (J) (D2xB1X10 10J Xenon Strobe Beacon), 73.4 cd UL1638 Private mode fire (D2xB1LD2 LED Beacon), 87 cd High power steady (D2xB1LD2 LED Beacon), 94.78 cd* – measured ref. to I.E.S. (D2xB1X05 5J Xenon Strobe Beacon)
Peak Intensity cd300,000 cd
LED life>60,000 hours
SynchronizationSynchronized 1Hz, 1.3Hz and 2Hz flash rates
Energy10 Joules (10Ws) (D2xB1X10 10J Xenon Strobe Beacon), 5 Joules (5Ws) (D2xB1X05 5J Xenon Strobe Beacon)
Flash rate1Hz (60 fpm) (D2xB1X10 10J Xenon Strobe Beacon, D2xB1X05 5J Xenon Strobe Beacon)
Peak Candela1,000,000 cd – calculated from energy (J) (D2xB1X10 10J Xenon Strobe Beacon), 101,784 cd* – measured ref. to I.E.S. (D2xB1X10 10J Xenon Strobe Beacon), 33,410 cd* – measured ref. to I.E.S. (D2xB1X05 5J Xenon Strobe Beacon), 500,000 cd – calculated from energy (J) (D2xB1X05 5J Xenon Strobe Beacon)
Maximum output116dB(A) @ 1 metre [107dB(A) @ 10ft/3m]
Nominal output112dB(A) @ 1m +/- 3dB – Tone 2 [103dB(A) @ 10ft/3m]
No. of tones64 (UKOOA / PFEER compliant)
No. of stages4
Volume controlAdjustable -12dB(A) [Tone 2]
Effective range125m/410ft @ 1KHz
Stage switchingAC units: common supply line, DC units: negative or positive
MountingPole mount kit included
Ingress protectionEN60529: IP66/67, UL50E / NEMA250: 4 / 4X / 3R / 13
Enclosure materialChromated & powder coated – corrosion proof, Marine grade aluminium LM6 – copper free
Enclosure colourRed or Grey, custom colours available on request
Lens materialBorosilicate glass dome & PC colour filter
Lens guard316 (A4) Stainless Steel dome guard as standard
Cable entries
Measurable gasesBrass/Nickel Plated/Stainless Steel plugs included
Grounding studM4
Terminals0.5 – 2.5mm2 (20-14 AWG) SAK 2.5 or BK12
Line monitoringBlocking diode included. EOL can be factory fitted
Installation temp-40 to +50°C [-40° to +122°F]
Storage temperature-40 to +70°C [-40° to +158°F]
Relative Humidity95% – Additional tropicalisation is recommended for applications where both high relative humidity and high ambient temperatures exist
SKU: E2S-D2xC4 Categories: , , Tag: