D1xS2H 128dB(A) Alarm Horn Sounder

Maximum output[118dB(A) @ 10ft/3m +/- 3dB], [119dB(A) @ 10ft/3m +/- 3dB], Class II Product version: D -15dB(A), High power level:128dB(A) @ 1m +/- 3dB, Medium power level: 127dB(A) @ 1m +/- 3dB
Nominal output[113dB(A) @ 10ft/3m] +/- 3dB, [117dB(A) @ 10ft/3m] +/- 3dB, Class II Product version: D -15dB(A), High power level:126dB(A) @ 1m +/- 3dB, Medium power level: 122dB(A) @ 1m +/- 3dB
No. of tones64 (UKOOA / PFEER compliant)
No. of stages4
Volume controlFull range
Effective range>350m/1148ft @ 1KHz
Voltage DC24Vdc (11.5-54Vdc)
Voltage AC230Vac (100-240Vac)
In rush815mA within 4ms @ 24Vdc
Stage switchingAC units:common supply line, DC units: positive or negative
Safety Integrity LevelSIL1 and SIL2 Route 2H IEC61508 (2010)
Ingress protectionEN60529: IP66/67, UL50E / NEMA250:4 / 4X / 3R / 13
Enclosure materialMarine grade LM6 aluminium alloy
Enclosure colourRed or Grey, custom colours available on request
Enclosure finishChromate & powder coated finish
Cable entriesThread adaptors available
Measurable gasesBrass, Nickel Plated or Stainless Steel
Terminals0.5 – 2.5mm2 (20-14AWG) – 12AWG solid core conductor, Pluggable & duplicated terminals
Line monitoringBlocking diode included, EOL Min. 500 Ohm 2w, or 3k3 Ohm 0.5w resistor, or diode (DC versions) can be fitted
Ground/Earth studM5
Installation temp-55 to +85°C [-67° to +185°F]
Storage temperature-55 to +85°C [-67° to +185°F]
Relative Humidity00%, 99
Vibration test35Hz for a duration 4Hr (UL464)
Jarring test3ft/lb Energy (UL464)
Impact test3x 5lb (UL464)
MTBF DC225.16 years / 1,972,386 hours – MIL 217
MTBF AC138.96 years / 1,217,285 hours – MIL 217
Weight4.6kg/10.1lbs
SKU: E2S-D1xS2H Categories: , , Tag: