D2xC4 Haz Loc LED/Xenon & Horn Alarm Bar
| Source |
Array of 4 x High Power Cree LEDs |
|---|---|
| Eff. Intensity cd |
180 cd UL1638 General signaling (D2xB1LD2 LED Beacon) ,73.4 cd UL1638 Private mode fire (D2xB1LD2 LED Beacon) ,87 cd High power steady (D2xB1LD2 LED Beacon) ,250 cd – calculated from energy (J) (D2xB1X05 5J Xenon Strobe Beacon) ,288.8 cd* – measured ref. to I.E.S. (D2xB1X10 10J Xenon Strobe Beacon) ,500 cd – calculated from energy (J) (D2xB1X10 10J Xenon Strobe Beacon) ,94.78 cd* – measured ref. to I.E.S. (D2xB1X05 5J Xenon Strobe Beacon) |
| Peak Intensity cd |
300,000 cd |
| LED life |
>60,000 hours |
| Synchronization |
Synchronized 1Hz, 1.3Hz and 2Hz flash rates |
| Energy |
10 Joules (10Ws) (D2xB1X10 10J Xenon Strobe Beacon) ,5 Joules (5Ws) (D2xB1X05 5J Xenon Strobe Beacon) |
| Flash rate |
1Hz (60 fpm) (D2xB1X10 10J Xenon Strobe Beacon, D2xB1X05 5J Xenon Strobe Beacon) |
| Peak Candela |
1,000,000 cd – calculated from energy (J) (D2xB1X10 10J Xenon Strobe Beacon) ,101,784 cd* – measured ref. to I.E.S. (D2xB1X10 10J Xenon Strobe Beacon) ,33,410 cd* – measured ref. to I.E.S. (D2xB1X05 5J Xenon Strobe Beacon) ,500,000 cd – calculated from energy (J) (D2xB1X05 5J Xenon Strobe Beacon) |
| Maximum output |
116dB(A) @ 1 metre [107dB(A) @ 10ft/3m] |
| Nominal output |
112dB(A) @ 1m +/- 3dB – Tone 2 [103dB(A) @ 10ft/3m] |
| No. of tones |
64 (UKOOA / PFEER compliant) |
| No. of stages |
4 |
| Volume control |
Adjustable -12dB(A) [Tone 2] |
| Effective range |
125m/410ft @ 1KHz |
| Stage switching |
AC units: common supply line ,DC units: negative or positive |
| Mounting |
Pole mount kit included |
| Ingress protection |
EN60529: IP66/67, UL50E / NEMA250: 4 / 4X / 3R / 13 |
| Enclosure material |
Chromated & powder coated – corrosion proof ,Marine grade aluminium LM6 – copper free |
| Enclosure colour |
Red or Grey, custom colours available on request |
| Lens material |
Borosilicate glass dome & PC colour filter |
| Lens guard |
316 (A4) Stainless Steel dome guard as standard |
| Cable entries | |
| Measurable gases |
Brass/Nickel Plated/Stainless Steel plugs included |
| Grounding stud |
M4 |
| Terminals |
0.5 – 2.5mm2 (20-14 AWG) SAK 2.5 or BK12 |
| Line monitoring |
Blocking diode included. EOL can be factory fitted |
| Installation temp |
-40 to +50°C [-40° to +122°F] |
| Storage temperature |
-40 to +70°C [-40° to +158°F] |
| Relative Humidity |
95% – Additional tropicalisation is recommended for applications where both high relative humidity and high ambient temperatures exist |
Related products
Need some help with your project?
Send an enquiry or contact us directly and we will try our best to help you.