Haes Esento Marine 12 Zone Conventional Fire Alarm Control Panel

The Haes Esento Marine 12 Zone is a conventional marine approved fire alarm control panel.

Haes Esento Marine 12 Zone Fire Alarm Control Panel

The Haes Esento Marine 12 Zone is a marine approved conventional fire alarm control panel designed to deliver reliable fire detection and alarm management for vessels on the sea. Approved by MED, Lloyd’s Register, and ABS, the panel meets marine industry requirements and is fitting for installation on a wide range of commercial, passenger, and offshore vessels.

Supporting 12 conventional detection zones, the Esento Marine 12 Zone combines advanced fire alarm functionality with direct operation. The panel includes programmable features such as muster alarm zone settings, false alarm management modes, programmable output delays, and networking capabilities for up to 8 control panels. It also supports fully functional repeater panels, making it ideal for larger vessels requiring centralized monitoring and control.

The control panel works with Apollo Orbis Marine detectors and incorporates comprehensive supervision features, including detector removal monitoring, earth fault monitoring, monitored sounder circuits, and programmable outputs. Access to critical controls can be locked using either a key switch or PIN code entry, helping to prevent unauthorized operation.

Key Features

  • 12 conventional fire detection zones
  • Marine approved (MED, Lloyd’s Register, ABS)
  • Network up to 8 control panels
  • Supports fully functional repeater panels
  • Key switch or code entry controlled operation
  • Compatible with Apollo Orbis Marine detectors
  • Integral detector removal monitoring
  • Earth fault monitoring
  • 3 Amp switch mode power supply
  • 4 monitored sounder outputs
  • 2 auxiliary voltage free change-over relays
  • Class change input
  • Alert input
  • Fire and fault switched negative outputs
  • Programmable output delays
  • False Alarm Management Modes A, B and C
  • Muster alarm functionality
  • Test mode with or without sounders
  • Disable zones, sounder outputs, auxiliary outputs and delays

Typical Applications

The Esento Marine 12 Zone provides reliable fire detection and alarm management for medium to large marine installations.

Common applications include:

  • Cargo vessels
  • Passenger ferries
  • Cruise ships
  • Offshore platforms
  • Offshore support vessels
  • Engine rooms
  • Accommodation areas
  • Machinery spaces

 

Technical Specifications

Parameter Specification
Product Name Haes Esento Marine 12 Zone
System Type Conventional Marine Fire Alarm Control Panel
Number of Zones 12
Marine Approvals MED, Lloyd’s Register, ABS
Networking Capacity Up to 8 Control Panels
Repeater Panel Support Yes
Detector Compatibility Apollo Orbis Marine Detectors
Power Supply 3 Amp Switch Mode PSU
Nominal Output Voltage 27 VDC
Sounder Outputs 4 Monitored Outputs
Auxiliary Relays 2 Voltage-Free Change-Over Relays
Fire Relay 1
Fault Relay 1
Auxiliary Inputs Class Change Input, Alert Input
Fault Monitoring Earth Fault Monitoring
Detector Monitoring Detector Removal Monitoring
False Alarm Modes A, B and C
Muster Alarm Yes
Output Delay Programming Yes
Test Function With or Without Sounders
Disable Functions Zones, Sounders, Aux Outputs and Delays
Alarm Load Capacity 2.4 A Shared Across All Sounder Outputs
Sounder Circuit Protection Resettable Fuses, 500 mA per Circuit

Installation Characteristics

Parameter Description
Control Panel Type Conventional Marine Fire Alarm Panel
Installation Environment Marine and Offshore Applications
User Access Key Switch or PIN Code
Network Support Up to 8 Panels
Detector Support Apollo Orbis Marine Range
Monitoring Functions Earth Fault and Detector Removal Monitoring
Alarm Management Muster Alarm, Output Delays and False Alarm Management
Typical Service Fire Detection and Alarm Control
SKU: Esento-Marine-12-Zone Categories: , , Tag: