| Coding | Ex db IIC T5 Gb Ta. -55° to +70°C (Dual switch), Ex db IIC T6 Gb Ta. -55°C to +60°C (Dual switch), Ex db IIC T6 Gb Ta. -55°C to +70°C (Single switch) |
|---|---|
| Switch | Sealed – IP67 |
| Ingress protection | EN/IEC 60529 – IP66/67 |
| Enclosure material | 316L Stainless Steel |
| Color | RAL3000 Red (others available on request) |
| Cable entries | 1 x M20x1.5 side., 2 x bottom and 1 x side entries, 2 x M20x1.5 top and, Back box can be rotated to give |
| Measurable gases | 2 x 316 Stainless Steel plugs as standard, Brass and Nickel plated plugs optional |
| Terminals | DIN rail 8 – 2.5mm2 SAK2.5 or, Termination board featuring 6 – 2.5mm2 terminals plus 4 x dedicated EOL & Series terminals |
| Earth | External M5 earth connection |
| Relative Humidity | R.H. 95% @ 20°C |
| Test | Test key facility |
| MTBF | 479.6 years / 4,201,680 hours – MIL 217 |
| Weight | 4.2Kg/9.26Ibs |