Cerberus FDM223 Manual Call Point

The Cerberus FDM223 Manual Call Point is designed for immediate manual actuation of a fire alarm.

The Cerberus FDM223 Manual Call Point is designed for immediate manual actuation of a fire alarm. It can be used for indoor and outdoor applications, and it is equally suited for wet, humid and dusty areas.

The Cerberus FDM223 can be used for surface and recess mounted feed lines in easily accessible places. To replace the glass plate, the housing must be opened with the key for the Manual Call Point. The push button must be reset before closing the housing again.

Operating temperature-25 to +70 °C
Working voltage12 – 33 Vdc
Colorred, RAL 3000
IP Rating(IP64 with protection seal), IP44
StandardsEN 54-11, EN 54-17
Dimensions134 x 134 x 43 mm
Storage temperature-30 to +75 °C
Humidity<95 % RH (no condensation)
Communication ProtocolFDnet/C-NET
Quiescent current200μA
Ext. alarm indicator2