Apollo XP95 Manual Call Point – red (55100-905APO)

The Apollo XP95 Manual Call Point (55100-905APO) has been designed to operate on a loop of intelligent Fire Detection devices and when activated interrupts the polling cycle for a very fast response.

The Apollo XP95 Manual Call Point (55100-905APO) has been designed to operate on a loop of intelligent Fire Detection devices and when activated interrupts the polling cycle for a very fast response. This Apollo Manual Call Point is intended for indoor applications.

A seven-segment DIL switch enables the addressing of each Call Point at commissioning stage. When operated, the Apollo Manual Call Point interrupts the polling cycle for a fast response. Bi-colored LEDs indicate isolate and normal conditions.

Features
‘Plug and Play’ terminal connections for fast wiring
Continuity link for wiring test before commissioning
Reports an alarm in under 0.2 seconds
Resettable element.

Warranty10 year
ColorRed
Weight151g
Materials housingABS, Polycarbonate
Length93mm (3.66in)
Width89mm (3.5in)
Height26.5mm (1.04in)
Detection principleOperation of a switch.
StandardsEN 54-11
ApprovalsCCCf, CPR, LPCB
Protocol voltage (max)9V
Protocol voltage (min)5V
Protocol voltage5 to 9V peak to peak
Power-up surge current1mA
Maximum power-up time1 second
Quiescent current100μA
Quiescent current tested at24V dc
Humidity (max)95% RH
Humidity (min)0% RH
Humidity0% to 95% (no condensation or icing)
Humidity Noteno condensation or icing
Operating temperature (min)-20°C (-4°F)
Operating temperature (max)60°C (140°F)
Operating temperature-20 to 60°C (-4 to 140°F)
IP rating ValueIP24
Storage temperature (min)-30°C
Storage temperature (max)80°C
Storage temperature-30 to 80°C
SKU: Apollo-55100-905APO Categories: , , Tag: