DISCOVERY MANUAL CALL POINT – OUTDOOR – ISOLATING 58200-951APO
| Warranty | 3 year |
|---|---|
| Color | Red |
| Weight | 325g |
| Materials housing | Polycarbonate |
| Length | 114mm (4.49in) |
| Width | 114mm (4.49in) |
| Height | 74mm (2.91in) |
| Detection principle | Operation of a switch. |
| Key type | Apollo Manal Call Point reset key |
| Standards | EN 54-11, EN 54-17 |
| Approvals | CPR, SBSC |
| Protocol voltage (max) | 9V |
| Protocol voltage (min) | 5V |
| Protocol voltage | 5 to 9V peak to peak |
| Power-up surge current | 1mA |
| Maximum power-up time | 1 second |
| Quiescent current | 100μA |
| Quiescent current tested at | 24V dc |
| Polarity | L1 & L2 are polarity sensitive |
| Humidity (max) | 95% RH |
| Humidity (min) | 0% RH |
| Humidity | 0% to 95% (no condensation or icing) |
| Humidity Note | no condensation or icing |
| Operating temperature (min) | 30°C (86°F) |
| Operating temperature (max) | 70°C (158°F) |
| Operating temperature | 30 to 70°C (86 to 158°F) |
| IP rating Value | IP67 |
Related products