The Apollo XP95 Manual Call Point (55100-905APO) has been designed to operate on a loop of intelligent Fire Detection devices and when activated interrupts the polling cycle for a very fast response.

The Apollo XP95 Manual Call Point (55100-905APO) has been designed to operate on a loop of intelligent Fire Detection devices and when activated interrupts the polling cycle for a very fast response. This Apollo Manual Call Point is intended for indoor applications.

A seven-segment DIL switch enables the addressing of each Call Point at commissioning stage. When operated, the Apollo Manual Call Point interrupts the polling cycle for a fast response. Bi-colored LEDs indicate isolate and normal conditions.

Features
‘Plug and Play’ terminal connections for fast wiring
Continuity link for wiring test before commissioning
Reports an alarm in under 0.2 seconds
Resettable element.

Warranty

10 year

Color

Red

Weight

151g

Materials housing

ABS

,

Polycarbonate

Length

93mm (3.66in)

Width

89mm (3.5in)

Height

26.5mm (1.04in)

Detection principle

Operation of a switch.

Standards

EN 54-11

Approvals

CCCf

,

CPR

,

LPCB

Protocol voltage (max)

9V

Protocol voltage (min)

5V

Protocol voltage

5 to 9V peak to peak

Power-up surge current

1mA

Maximum power-up time

1 second

Quiescent current

100μA

Quiescent current tested at

24V dc

Humidity (max)

95% RH

Humidity (min)

0% RH

Humidity

0% to 95% (no condensation or icing)

Humidity Note

no condensation or icing

Operating temperature (min)

-20°C (-4°F)

Operating temperature (max)

60°C (140°F)

Operating temperature

-20 to 60°C (-4 to 140°F)

IP rating Value

IP24

Storage temperature (min)

-30°C

Storage temperature (max)

80°C

Storage temperature

-30 to 80°C