AutroGuard V-530-EXIC Multicriteria Protector

Part no.

V-530-EXIC

The AutroGuard V-530-EXIC is a SIL2-certified multicriteria fire detector designed for use in Zone 2 hazardous areas.

Request a quote

Add this product to your RFQ list. No account needed.

AutroGuard V-530-EXIC Multicriteria Protector

The AutroGuard V-530-EXIC is a SIL2-certified multicriteria fire detector designed for use in Zone 2 hazardous areas. As part of the AutroGuard V-530 series, it combines advanced optical smoke detection and heat detection technologies in a compact, addressable device that provides reliable fire detection while minimizing nuisance alarms.

Using DYFI3D MultiAngle/MultiWavelength sensing technology, the detector analyzes smoke and heat signatures with advanced algorithms to distinguish genuine fire conditions from environmental influences. The V-530-EXIC incorporates SelfVerify and Cover Detection as standard features, providing continuous supervision and helping to ensure reliable fire detection throughout the product lifecycle.

Important: Required hazardous-area certification (ATEX, IECEx, CSA, or INMETRO) must be specified when ordering.

Key Features

  • SIL2 certified according to IEC 61508
  • Intrinsically safe Ex ic design for Zone 2 areas
  • MultiAngle/MultiWavelength optical smoke sensing
  • Rate-of-rise heat detection
  • DYFI3D® fire recognition technology
  • SelfVerify® automatic detector testing as standard
  • Cover Detection functionality as standard
  • Three smoke sensitivity classes
  • Six certified heat response categories
  • Automatic detector addressing
  • Integrated short-circuit isolator in the base
  • Ultra-low current consumption
  • 360° visible dual-colour LED indication
  • Suitable for hazardous industrial, marine, and offshore applications

Typical Applications

The AutroGuard V-530-EXIC is ideal for:

  • Offshore oil and gas facilities
  • Marine vessels
  • LNG and LPG terminals
  • Fuel handling systems
  • Chemical storage facilities
  • Hazardous utility spaces
  • Process plants
  • Refineries
  • Industrial production areas

Technical Specifications

Specification Details
Product AutroGuard® V-530-EXIC
Part Number 116-V-530-EXIC
Type SIL2-Certified Multicriteria Fire Detector
Hazardous Area Rating Ex ic
Zone Classification Zone 2
Functional Safety IEC 61508 SIL2
Detection Technologies Optical Smoke and Heat Detection
Smoke Sensitivity Classes High, Medium, Low
Heat Response Categories A1, A1S, A1R, A2S, B, C
Integrated Sounder No
Integrated VAD No
Addressing Automatic Addressing in Base
Status Indication 360° Dual-Colour LED (Red/Yellow)
Weight 127 g (172 g including base)
Ingress Protection IP44D (IP55 with conduit box)
Operating Voltage 10–26 VDC
Operating Temperature -30°C to +70°C
Operating Temperature (Heat Only Mode) Up to +80°C
Operating Humidity 10–95% RH (Non-Condensing)
Housing Material PC ABS, UL94 V-0
Colour White (RAL 9010)
Country of Origin Norway

Downloads for AutroGuard V-530-EXIC Multicriteria Protector.

Below you will find all downloads available for the AutroGuard V-530-EXIC Multicriteria Protector. If you need any help in finding a file that is not in this list, please do not hesitate to contact us.
There are currently no downloads available for AutroGuard V-530-EXIC Multicriteria Protector.

Related products

Need some help with your project?

Send an enquiry or contact us directly and we will try our best to help you.