The Tyco 555.800.002 CIM800 is an addressable contact input module, designed to fit in the standard ancilliary housings.
Tyco CIM800 Contact Input Module (555.800.002)
The Tyco CIM800 (555.800.002) is an addressable contact input module designed to provide a simple and reliable way to connect external devices to Tyco MX fire alarm systems. Housed within the standard ancillary enclosure range, it allows engineers to monitor the status of external equipment and transmit this information directly to the fire alarm control panel.
The CIM800 provides two monitored input circuits, which can be configured as either two separate spur circuits (Style B) or a single loop circuit (Style A). Furthermore, both inputs support normally open (NO) and normally closed (NC) monitoring, providing greater flexibility during installation.
In addition, the module continuously supervises the input wiring for faults. Engineers can configure the inputs to generate either an alarm condition or a short-circuit fault warning if a fault occurs on normally open monitoring circuits. As a result, the CIM800 helps maintain reliable system performance while providing clear fault indication.
Key Features
- Addressable contact input module for MX fire alarm systems
- Provides two monitored input circuits
- Supports Style A (loop) and Style B (spur) wiring configurations
- Compatible with normally open and normally closed contacts
- Monitors wiring for open- and short-circuit conditions
- Configurable alarm and fault reporting options
- Fits standard Tyco ancillary housings
- Enables integration of external equipment with the fire alarm system
- Simple installation and configuration
Specifications
- Loop Voltage: 20V to 40V DC
- Quiescent Current: 275µA
- Alarm State Current: 2.8mA
- Circuit Resistance: 10Ω
- End-of-Line Resistor: 200Ω
- Alarm Resistance (Short-Circuit Fault): 100Ω
- Maximum Modules per Loop: 200/250
- Operating Temperature: -25°C to +70°C
- Storage Temperature: -40°C to +80°C
- Relative Humidity: 10% to 95% (non-condensing)
The Tyco CIM800 allows engineers to monitor external contacts and field devices efficiently, helping to expand system functionality while maintaining reliable supervision and fault monitoring.
Technical Specifications
| Parameter | Specification |
|---|---|
| Product Name | Tyco CIM800 Contact Input Module |
| Part Number | 555.800.002 |
| Device Type | Addressable Contact Input Module |
| Function | Supervised Contact Monitoring |
| System Compatibility | Tyco Minerva MX / MZX Technology Systems |
| Communication | Addressable Loop Protocol |
| Power Supply | Loop Powered |
| Input Type | Volt-Free Contact Input |
| Monitoring | Alarm, Fault & Status Conditions |
| Application | Third-Party Equipment Monitoring |