Autronica BF-502-EX Manual Call Point

Part no.

Autronica-BF-502-EX

The Autronica BF-502-EX is an addressable break-glass manual call point with SelfVerify technology.

Request a quote

Add this product to your RFQ list. No account needed.

Autronica BF-502-EX Manual Call Point with SelfVerify

The Autronica BF-502-EX is an addressable break-glass manual call point with SelfVerify technology, designed for use in hazardous areas classified as Zone 0, Zone 1, Zone 2, Zone 20, Zone 21, and Zone 22. Developed for Autronica’s interactive fire detection systems, the call point provides reliable manual fire alarm activation while reducing maintenance requirements through automatic self-testing.

The BF-502-EX must be connected via an approved BZ-500 barrier and is built to withstand harsh industrial, marine, and offshore environments. Its corrosion-resistant glass-reinforced polyester (GRP) enclosure and IP66/IP67 ingress protection rating ensure dependable performance in outdoor and exposed locations.

The integrated SelfVerify function automatically tests the call point every 24 hours, verifying its ability to initiate an alarm and significantly reducing the need for manual functional testing. Alarm activation occurs when the glass is broken, triggering the internal alarm switch. The unit is reset by replacing the broken glass element.

Key Features

  • Addressable break-glass manual call point
  • Approved for hazardous areas Zone 0, 1, 2, 20, 21, and 22
  • Requires approved BZ-500 barrier
  • SelfVerify automatic testing every 24 hours
  • Corrosion-resistant GRP housing
  • IP66 and IP67 environmental protection
  • Integrated short-circuit isolator
  • Automatic addressing
  • Proven Autronica detection technology
  • Suitable for outdoor installations
  • Designed to meet requirements of major maritime classification societies
  • Reduced maintenance and testing requirements

Typical Applications

The BF-502-EX is suitable for:

  • Offshore platforms and FPSOs
  • Oil and gas production facilities
  • Chemical and petrochemical plants
  • Marine vessels and engine rooms
  • Refineries
  • Tank farms and storage terminals
  • Process industries
  • Hazardous areas with gas and dust explosion risks
  • Escape routes, stairwells, landings, and emergency exits
  • Industrial and commercial facilities requiring hazardous-area fire alarm activation

Technical Specifications

Specification Details
Product Type Addressable Break-Glass Manual Call Point
Model BF-502-EX
Hazardous Area Classification Zone 0, 1, 2, 20, 21, 22
Protection Method Ex ia
System Compatibility Autronica Interactive Fire Detection Systems
Barrier Requirement BZ-500
Activation Method Break-glass operation
Reset Method Replace glass element
Self-Test Function SelfVerify (automatic every 24 hours)
Addressing Automatic
Short Circuit Isolator Integrated
Operating Voltage 10–27 VDC
Standby Current Consumption 0.3 mA
Degree of Protection IP66 / IP67
Housing Material Glass-reinforced polyester (GRP)
Colour Red
Weight 0.5 kg
Cable Entries 2 × M20
Operating Temperature -20°C to +70°C
Storage Temperature -55°C to +70°C
Maintenance Replace broken glass when operated
Service Replace unit if faulty
Environmental Standard EN 54
ATEX Certificate NEMKO 03ATEX218X
IECEx Certificate IECEx NEM 11.0009X
Notified Body Nemko (0470)

Downloads for Autronica BF-502-EX Manual Call Point.

Below you will find all downloads available for the Autronica BF-502-EX Manual Call Point. If you need any help in finding a file that is not in this list, please do not hesitate to contact us.
There are currently no downloads available for Autronica BF-502-EX Manual Call Point.

Related products

Need some help with your project?

Send an enquiry or contact us directly and we will try our best to help you.