D1xC1X10F 115dB(A) Alarm Horn & 10J Xenon Strobe

Maximum output115dB(A) @ 1 metre [106dB(A) @ 10ft/3m]
Nominal output110dB(A) @ 1m +/- 3dB – Tone 4 [101dB(A) @ 10ft/3m]
No. of tones64 (UKOOA / PFEER compliant)
No. of stages4
Volume controlFull range
Effective range125m/410ft @ 1KHz
Voltage DC24Vdc (20-28Vdc)
Voltage AC110-120Vac, 220-240Vac
Stage switchingAC units: common supply line, DC units: negative or positive
Energy10 Joules (10Ws)
Flash ratesOption 1: 1Hz (60 fpm), Option 2: 1.5Hz (90 fpm), Option 3: Double Strike
Peak Candela1,000,000 cd – calculated from energy (J), 85,544 cd* – measured ref. to I.E.S.
Eff. Intensity cd260 cd* – measured ref. to I.E.S., 500 cd – calculated from energy (J)
Lens coloursAmber, Blue, Clear, Green, Magenta, Red & Yellow
Tube lifeEmissions reduced to 70% > 5 million flashes
Safety Integrity LevelSIL1 and SIL2 Route 2H IEC61508 (2010)
Ingress protectionEN60529: IP66/67, UL50E / NEMA250: 4 / 4X / 3R / 13
Enclosure materialChromated & powder coated – corrosion proof, Marine grade aluminium LM6 – copper free
Enclosure colourRed or Grey, custom colours available on request
Cable entries
Terminals0.5 – 2.5mm2 (20-14 AWG) Pluggable, duplicated terminals
Grounding studM5
Line monitoringBlocking diode included. EOL Min. 500 Ohm 2W, or 3k3 Ohm 0.5W resistor or diode (DC versions) can be fitted
Installation temp-55 to +85°C [-67° to +185°F]
Storage temperature-55 to +85°C [-67° to +185°F]
Relative Humidity95% – Additional tropicalisation is recommended for applications where both high relative humidity and high ambient temperatures exist
Vibration test35Hz for a duration 4Hr (UL464)
Jarring test3ft/lb Energy (UL464)
Impact test3x 5lb (UL464)
Weight5.2kg/11.4lbs