Consilium Salwico NS-AOS-IS N1148 Intrinsically Safe Optical Smoke Detector

The Consilium Salwico NS-AOS-IS N1148 is an intrinsically safe analogue addressable optical smoke detector for Salwico fire alarm systems CS3000, CS4000, NSAC-1 and TERRA FIRE.

The Consilium Salwico NS-AOS-IS N1148 is an intrinsically safe analogue addressable optical smoke detector for Salwico fire alarm systems CS3000, CS4000, NSAC-1 and TERRA FIRE.

The Salwico NS-AOS-IS is connected via an intrisically safe isolator. The alarm condition is indicated via a red LED. The LED remains lit until the alarm has been reset on the control panel.

The address is set by an 8-way DIP-switch, which is mounted on the backside of the detector. The NS-AOS-IS is connected to the detector loop via an intrinsically safe isolator. It is not possible to connect any remote LED indicator to NS-AOS-IS.

Working voltage

15-28 VDC

Working current

0.2 mA

Operating current - Alarm

2.5 mA

Temperature range

-10 °C to +50 °C

Ambient Humidity

0-95 % RH non condensing

Color

White

Weight

100g

Ex Class

II 1 G, EEx ia II C T5

Systems

CS3000, CS4000, NSAC-1, Salwico Cargo, Salwico Cruise, Salwico Ro/Pax, Salwico Workboat, Salwico Yacht