The Cerberus LaserFOCUS VLF-250 Detector is a very early warning Smoke Detector (aspirating Smoke Detector ASD) designed to protect small‚ business-critical environments of less than 250 m2.

The Cerberus LaserFOCUS VLF-250 Smoke Detector works by continually drawing air into sampling holes in a pipe network. The air is filtered and passed into a detection chamber where light-scattering technology detects the presence of very small amounts of smoke. The Cerberus LaserFOCUS VLF-250 Detector status information is communicated on the detector display. The FDnet/C-NET interface card is integrated.

Cerberus LaserFOCUS VLF-250
 
Please contact us for more information.

The Cerberus LaserFOCUS VLF-250  is a very early warning Smoke Detector (aspirating Smoke Detector ASD) designed to protect small‚ business-critical environments of less than 250 m2.
Communication protocol: FDnet/C-NET
Operating voltage: DC 18…30 V
Quiescent current : 220 mA
Alarm current: 295 mA
Display:

 
4 Alarm state indicators
Fault and disabled indicators
Smoke level indicator
Area coverage: Up to 250 m2
Alarm threshold:

 
0.025 - 2.00 %/m / info alarm‚
pre-alarm
0.025 - 20.00 %/m / fire 1‚ fire 2
Air inlet pipe:

 
Accepts both metric and
American standard pipe sizes
External diameter 25 mm
Internal diameter 21 mm
Pipe length:


 
max. 1 x 25 m
(max. 12 holes)
max. 2 x 15 m per branch
(max. 6 holes per branch)
Relay outputs:
 
3x 2 A / 30 V
Pre-alarm‚ alarm‚ fault
Terminals: 0.2…2.5 mm2 (30…12 AWG)
Dimensions (W x H x D): 255 x 185 x 90 mm
Operating temperature: 0...+40 °C
Humidity: L95 % RH (no condensation)
Ingress Protection: IP30