Ampac 4210-0006 2-Wire Network Interface Board


The Ampac 4210-0006 is a 2-wire Network Interface Board which allows up to 99 FireFinder PLUS panels (nodes) to be connected in a high integrity redundant network configuration. The network can withstand an open or short circuit fault without the loss of communications to any nodes. The cable between each node can be up to 1.2km.
Ampac 4210-0006 2-Wire Network Interface Board
The network operates as a peer-to-peer network, with all of the device state changes shared over the network. Each of the nodes can be configured as to which state changes are displayed. This configuration is specified in terms of nodes, loops, or groups.

The network also supports compressed file transfer for the application software and configuration file. Using this facility all nodes can have their application software and configuration updated simultaneously. Configuration of the network is handled by the ConfigManager Plus Windows application.

Please contact us for more information.

Supports redundant network with isolated network in and out ports.
Up to 99 network nodes.
115200 Baud Rate.
The distance between nodes is 1.2km.
Diagnostic LEDs.
Operating Voltage 27 VDC
Quiescent Current 41 mA
Max Nodes 99
Protocol RS485
Recommended Cable 2 Core, Screened Fire Resistant
Cable Length Node to Node 1.2 km
Temperature -5ºC to + 40ºC