Tyco 555.800.002 CIM800 Contact Input Module Minerva MX

The Tyco 555.800.002 CIM800 is an addressable contact input module, designed to fit in the standard ancilliary housings.

The Tyco 555.800.002 CIM800 is an addressable contact input module, designed to fit in the standard ancilliary housings. The Tyco CIM800 provides two inputs to current MX panels though this can be implemented as two seperately wired spurs (style B) or as a loop (style A) Both spur and loop input wiring can be configured to monitor normally open or normally closed inputs.

In addition both can be configured to initiate an alarm or shot circuit fault message in the event of a short circuit on normally open monitoring circuits.

Features
Loop Voltage1 20V to 40Vdc
Quiescent Current 275µA
Alarm State Current 2.8mA
Circuit Resistance 10 Ohm
EOL Resistor 200 Ohm
Alarm Resistance (s/c fault) 100 Ohm
Max. CIM800 per Loop2 200/250
Ambient Temperature –25°C to +70°C
Storage Temperature –40°C to +80°C
Relative Humidity 10% to 95% (non cond.)

Loop Voltage

20V to 40Vdc

Quiescent current

275µA

Alarm Current

2.8mA

Input Cable Length

1m (maximum)

Environment

Indoor Application

Temperature

-25°C to + 70°C

Storage temperature

-40°C to +80°C

Relative Humidity

10% to 95% (non cond.)

Dimensions

61 x 84 x 25 mm

Weight

22g

ActivFire Listing

afp-1446 (MIM800)

Circuit Resistance

10 Ohm

End of Line Resistor

200 Ohm

Alarm resistance

100 Ohm

Max. CIM800 per Loop

200/250

Wire Size (maximum)

2.5sq. mm

SKU: 555.800.002 Categories: , , Tag: