Cerberus FDM223 Manual Call Point


The Cerberus FDM223 Manual Call Point is designed for immediate manual actuation of a fire alarm. It can be used for indoor and outdoor applications, and it is equally suited for wet, humid and dusty areas. It can be used for surface and recess mounted feed lines in easily accessible places. To replace the glass plate, the housing must be opened with the key for the manual call point. The push button must be reset before closing the housing again.

Cerberus FDM223 Manual Call Point

Technical specification
Operating temperature -25 to +70 °C
Operating voltage 12 - 33 VDC
Colour red, RAL 3000
Protection category IP44 (IP64 with protection seal)
Standard EN 54-11, EN 54-17
Dimensions (W x H x D) 134 x 134 x 43 mm
Storage temperature -30 to +75 °C
Relative humidity <95 % (no condensation)
Communication protocol FDnet/C-NET
Quiescent current 200 μA
Ext. alarm indicator 2