NetSafety UV/IRS Flame Detector


The NetSafety UV/IRS Flame Detector delivers an exceptional performance with many distinct functions and features. To initiate a fire condition, two precise spectrums of radiation must be recognized and confirmed by highly tuned sensors. The accurate and reliable flame monitoring technology, combined with immunity to arc welding, hot body radiation, lightning and sunlight greatly reduces costly false alarms while providing critical safety performance.

The NetSafety UV/IRS Flame Detector can be used as an replacement for the NetSafety Phoenix Triple IR Flame Detector.

NetSafety UV/IRS Flame Detector

The NetSafety UV/IRS uses the latest in modular microprocessor and Ultraviolet/Infrared sensor technology, which ensures accurate and reliable monitoring for hydrocarbon based fires. The NetSafety UV/IRS can be used as a stand-alone detector, or can be connected to a variety of networked safety systems to create a dependable fire monitoring system.
 

Specifications
Article Code Description
Response Time <6 sec (dependent on fuel source, fire size, distance)
Field of View 120 degrees horizontal / 95 degrees vertical
Spectral Range
 
UV Radiation 185 to 260 nanometres (1850 to 2600 angstroms) | IR Radiation in the 4.4 micron range
Sensitivity Settings High/Med-High/Med/Low (Field Selectable via dipswitches)
 
Time Delay 0, 3, 5, 7 seconds (Field Selectable via dipswitches)
Temperature -50°C to +75°C (-58°F to 167°F)
IP/NEMA Rating IP66 - NEMA 4X
Metallurgy Aluminum or 316 SS
Voltage Range 10 - 32 VDC
Power Consumption Analogue model - Nom 1.1W / Max 2.76W (@24VDC)
 
Relative Humidity 0-95%, Non-condensing


Please contact us for more information.