Dräger Flame 1700 Flame Detector


The Dräger Flame 1700 is an UV Flame Detector, designed for the detection of non-organic based fires such as hydrogen and metals as well as organic based fires. This Draeger Flame Detector provides flexibility with its numerous output modes, and advanced design features ensure reliability and speed in the detection of such fires.

Dräger Flame 1700 Flame Detector

Please contact us for more information.
Benefits:
Simple installation
The Dräger Flame 1700 is easily installed with a stainless steel mounting bracket; this can be rotated to ensure optimum positioning of the detector in relation to the potential fire source. Angular markings allow the positioning angles of the detector to be recorded for future reference.

Detector flexibility
As well as a 4 to 20 mA output and 3 relays, an optional RS 485 output is also available, which can be multi-dropped to a central location. This provides a number of options for detector monitoring and the
triggering of the necessary control action upon the detection of a fire.

Automatic and manual optics checks
Automatic checks of the detector electronics and optics ensure no fault goes undetected. Additionally the test can be triggered manually at any time.

Isolated 4 to 20 mA as standard
Complete flexibility enables the detector to be operated from a separate power supply (as a 4 wire device) or as a 3 wire device where there is no requirement for an isolated output.

Easily visible status LED
A tri-colored LED which is visible at the front of the Flame Detector provides a simple status indication to personnel in close proximity to the detector. Green indicates normal operation; yellow indicates a fault and red indicates the presence of radiation.

Worldwide approvals
The Dräger Flame 1700 Flame Detector can be used worldwide with the following approvals: ATEX, IECEx, FM and CSA.
Type: Explosion-proof UV Flame Detector
for hydrocarbon and non-hydrocarbon based fires
Spectral response: 0.185 to 0.26 micron
Field of view: Horizontal 90°, vertical 90°
Sensitivity: 0.1 m2 gasoline fire at 18 meters,
1 sq. foot fire at 60 feet
Response time t90: 1 second, typical, configurable up to 30 seconds
Signal output: Fault: 0 mA
Optics/electronics check failure: 2 mA
Normal operation: 4 mA
Fire pre-warning: 16 mA
Fire: 20 mA (factory configurable
for latching/non-latching alarm)
3 relays for fault, alarm and accessory,
125 VAC, 0.5 A; 30 VDC, 2 A
optional RS 485
Supply voltage: 18 to 32 VDC, current consumption 160 mA
quiescent state at 24 VDC
Temperature: -40 to 70°C, -40 to + 158°F
Pressure: 915 to 1055 hPa, 27.9 to 31.2 inch of Hg
Humidity: 0 to 99 % RH, non-condensing
Enclosure: IP 66/NEMA 4X
Cable entry: M20, M25, 1/2” NPT or 3/4” NPT
Size (L x D, approx.): 275 mm x 155 mm, 10.8” x 6.1”
Weight (approx.): 3.5 kg, 7.7 lbs
Approvals: ATEX: II 2G EEx d IIC T6/T5 ;
- 50 ≤ Tamb ≤ + 60/+ 70°C
IECEx: Ex d IIC T6/T5 ;
- 50 ≤ Tamb ≤ + 60/+ 70°C
FM/CSA: Class I, Groups A, B, C, D
Class I, Zone 1, Groups IIA, IIB & IIC
Ex d II C; T6/T5; - 40 ≤ Tamb ≤ + 60/+ 70°C